How to Find the Proper Size of Wire & Cable In Metric & Imperial Systems

How to Determine the Suitable Size of Wire and Cable or Electrical Wiring Installation? Examples in Imperial and Metric Systems Based on NEC, IEC and IEEE.

The following step-by-step guide will show you how to calculate the correct size of cable and wire, or any other conductor, for electrical wiring installations with solved examples in both British or English and SI Systems, i.e., Imperial and Metric Systems, respectively.

Keep in mind that selecting the proper wire size is crucial when sizing a wire for electrical installations. An inappropriate size of wire for larger loads with high current may lead to chaos, resulting in the failure of electrical equipment, hazardous fires, and serious injuries.

Factors Affecting the Wire Size

Voltage Drop in a Cables

We know that all conductors, wires and cables (except superconductors) have some amount of resistance.

This resistance is directly proportional to the length and inversely proportional to the diameter of conductor i.e.

R ∝ l/a … [Ohm’s laws of resistance R = ρ (L÷ a)]

Whenever current flows through a conductor, a voltage drop occurs. Generally, voltage drop may be neglected for short lengths of conductors. However, in the case of lower diameter and long-length conductors, we must take into account the considerable voltage drops for proper wiring installation and future load management.

According to the NEC – 310-16, add 20% of additional ampacity for every 100 feet of distance (for example between main panel and subpanel) to counter the voltage drop.

According tot the IEEE rule B-23, at any point between power supply terminal and installation, Voltage drop should not increase above 2.5% of the provided (supply) voltage.

Related Posts:

How to Find The Suitable Size of Cable & Wire for Electrical Wiring Installation (Solved Examples in British and SI System)

Example:

If the supply voltage is 230V AC, then the value of allowable voltage drop should be;

Similarly, if the supply voltage is 120V AC, the allowable voltage drop should be no more than 3V for separate branch circuit (120V 2.5%) and 5% for feeder and branch circuits (120V 5%). Refer to the NEC Code – 310-16 which stats 20% of additional ampacity for every 100 feet of distance should be added to counter the voltage drop in the circuit.

In electrical wiring circuits, voltage drops also occur from the distribution board to the different sub circuit and final sub circuits, but for sub circuits and final sub circuits, the value of voltage drop should be half of that allowable voltage drops (i.e. 2.75V of 5.5V as calculated above)

Normally, Voltage drop in tables is described in Ampere per meter (A/m) e.g. what would be the voltage drop in a one meter cable which caries one Ampere current?

There are two methods to define the voltage drop in a cable which we will discus below.

In SI (System international and metric system) voltage drop is described by ampere per meter (A/m).

In FPS (foot pound system) voltage drop is described in length based which is 100 feet.

Related Posts:

How to Find the Voltage Drop in a Cable?

To find voltage drop in a cable, follow the simple steps given below.

(Stay cool :) We will follow both methods and systems for finding voltage drops (in meters and 100 feet) in our solved example for whole electrical installation wiring).

(Actual length of circuit volt drop for 1m) /100 ===> to find Volt drop in per meter.
(Actual length of circuit volt drop for 100ft) /100 ===> to find volt drop in 100 feet.

Load factor = Load Current to be taken by Cable/ Rated Current of Cable given in the table.

Related Posts:

How to Determine the Proper Cable & Wire Size for a Given Load?

Below are solved examples demonstrating how to find the proper cable size for a given load.

For a given load, cable size may be determined using various IEC and NEC tables (such Article 310 – Table – 310.15 (B) 16. However, it is crucial to keep in mind the role of ambient temperature and voltage drop for distance between main panel and subpanel.

When determining the size of cable for a given load, take into account the following general rules of thumbs.

Related Posts:

  1. Electrical Cable & Wire Size Calculator for Copper & Aluminum
  2. Wire & Cable Size in AWG Calculator for 1 and 3-Phase Load
  3. Voltage Drop in Wire & Cable Calculator

Solved Examples of Proper Cable & Wire Size

The following examples illustrate how to determine the proper size of cables for electrical wiring installations. These examples will make it easy to understand the method of determining the proper cable size for a given load in both single phase ad three phase wiring installations.

Example 1 – (Imperial System Followed by NEC)

What is the right size of wire for a 1,920 W load circuit supplied by 120V AC at 60°C (140°F)?

Solution:

First of all, let’s determine the current in amperes using basic Ohm’s Law that will flow from the 120V breaker to the 1.92kW load.

I (in Amps) = P (in Watts) ÷ V (in Volts)

I = 1,920 W ÷ 120 V

I = 16 Amp

Now, add a safety factor of 1.25 (based on 125% rule also known as continues load rule), as per NEC Code 220-2 for branch circuits, feeders, and service loads. This code specifies that only 80% of the branch circuit load should be connected to the circuit for the ampacity of the wire for any load. For instance, a 10-ampere breaker should be used for an 8-ampere load point. This way:

I = 16 amp 1.25

or 16 amp  125%

I = 20 Amp.

Now, If you see in the AWG wire size chart and NEC Table 310-15B (16) Article 310.60 (given below), the right size for 20 amp circuit is #12 AWG.

Example 2 – (240V and Distance Involved – NEC)

Find the Proper wire size for 2,400 W load circuit supplied by 240V single phase at a distance of 100 feet?

Solution:

Find the current using the following formula (same as mentioned above)

Current = Power ÷ Voltage

I = 2,400 W ÷ 240 V

I = 10 Amperes

Now, multiply the safety factor of 1.25 (80% of load should be connected of the rated ampacity) to the calculated amperage.

As the circuit is 100ft away, add additional 20% ampacity to the calculated value (according to the NEC Code – 310-16) to counter the voltage drop in the circuit.

Total Amps = 12.5A + 2.5A = 15 Amperes.

According to NEC table 310-15B and AWG wire size chart, the suitable wire size for 15 amp circuit is #14 AWG for copper at 60°C (140°F). If you are going to use aluminum, you may use #12 AWG aluminum wire.

Notes:

  1. The above calculation is based on NEC Table 310.15(B)(16) (formerly Table 310.16) with the help of 240.4(A) through (G) which shows the 14 AWG wire size is able to carry 15A at 60°C (140°F) and 20A at 75°C (167°F).
  2. The determined wire size, breaker rating, and ampacity in the above calculation for North America and Canada comply with the National Electrical Code (NEC) – Sections 210.19(A), 215.2, and 230.42(A) for continuous and non-continuous loads and 110.14(C) for ambient temperature rating.

Warning:

Example 3 – (Imperial, British or English System – IEC)

For an electrical wiring installation in a building, where the total load is 4.5kW and the total length of cable from the energy meter to the sub-circuit distribution board is 35 feet, with a supply voltage of 220V and a temperature of 40°C (104°F), find the most suitable size of cable if wiring is installed in conduits.

Solution:

Now select the size of cable for load current of 24.5A (from Table 1) which is 7/0.036 (28 Amperes). It means we can use 7/0.036 cable according to table 1.

Now, check the selected (7/0.036) cable with the temperature factor in Table 3. The temperature factor is 0.94 (from Table 3) at 40°C (104°F), and the current carrying capacity of (7/0.036) is 28A. Therefore, the current carrying capacity of this cable at 40°C (104°F) would be:

Current rating for 40°C (104°F) = 28 0.94 = 26.32 Amp.

Since the calculated value (26.32 Amp) at 40°C (104°F) is less than the current carrying capacity of the (7/0.036) cable, which is 28A, this size of cable (7/0.036) is also suitable with respect to temperature.

Now find the voltage drop for 100 feet for this (7/0.036) cable from Table 4 which is 7V, But in our case, the length of cable is 35 feet. Therefore, the voltage drop for 35 feet cable would be;

Actual Voltage drop for 35 feet = (7 35/100) (24.5/28) = 2.1V

And Allowable voltage drop = (2.5 220)/100 = 5.5V

Here, the actual voltage drop (2.1V) is less than the maximum allowable voltage drop of 5.5V. Therefore, the most appropriate and suitable cable size for that given load in the electrical wiring installation is (7/0.036).

Related Posts:

Example 4 – (SI / Metric / Decimal System – IEC)

What type and size of cable suits for given situation

Solution:

Load = 5.8kW = 5800W

Voltage = 230V

Current = I = P/V = 5800 / 230 = 25.2A

20% additional load current = (20/100) 5.2A = 5A

Total Load Current = 25.2A + 5A = 30.2A

Now select the size of cable for load current of 30.2A (from Table 1) which is 7/1.04 (31 Amperes). It means we can use 7/0.036 cable according to the table 1.

Now check the selected (7/1.04) cable with temperature factor in Table 3, so the temperature factor is 0.97 (in table 3) at 35°C (95°F) and current carrying capacity of (7/1.04) is 31A, therefore, current carrying capacity of this cable at 40°C (104°F) would be;

Current rating for 35°C (95°F) = 31 0.97 = 30 Amp.

Since the calculated value (30 Amp) at 35°C (95°F) is less than that of current carrying capacity of (7/1.04) cable which is 31A, therefore this size of cable (7/1.04) is also suitable with respect to temperature.

Now find the voltage drop for per ampere meter for this (7/1.04) cable from (Table 5) which is 7mV, But in our case, the length of cable is 35 meter. Therefore, the voltage drop for 35 meter cable would be:

Actual Voltage drop for 35meter =

= mV I L

= (7/1000) 30×35 = 7.6V

And Allowable voltage drop = (2.5 230)/100 = 5.75V

Here the actual Voltage drop (7.35V) is greater than that of maximum allowable voltage drop of 5.75V. Therefore, this is not a suitable size of cable for that given load. So we will select the next size of selected cable (7/1.04) which is 7/1.35 and find the voltage drop again.

According to Table (5) the current rating of 7/1.35 is 40 Amperes and the voltage drop in per ampere meter is 4.1 mV (See table (5)). Therefore, the actual voltage drop for 35 meter cable would be;

Actual Voltage drop for 35 meter =

= mV I L

(4.1/1000) 40×35 = 7.35V = 5.74V

This drop is less than that of maximum allowable voltage drop. So this is the most appropriate and suitable cable or wire size.

Related Posts:

Example 5

Following Loads are connected in a building:-

Sub-Circuit 1

Sub-Circuit 2

If supply voltages are 230 V AC, then calculate circuit current and Cable size for each Sub-Circuit?

Solution:

Total load of Sub-Circuit 1

= (2 1000) + (4 80) + (2×120)

= 2000W + 320W + 240W = 2560W

Current for Sub-Circuit 1 = I = P/V = 2560/230 = 11.1A

Total load of Sub-Circuit 2

= (6 80) + (5 100) + (4 800)

= 480W + 500W + 3200W= 4180W

Current for Sub-Circuit 2 = I = P/V = 4180/230 = 18.1A

Therefore, Cable suggested for sub circuit 1 = 3/.029” (13 Amp) or 1/1.38 mm (13 Amp)

Cable suggested for Sub-Circuit 2 = 7/.029” (21 Amp) or 7/0.85 mm (24 Amp)

Total Current drawn by both Sub-Circuits = 11.1A + 18.1A = 29.27 A

Therefore, cable suggested for Main-Circuit = 7/.044″ (34 Amp) or 7/1.04 mm (31 Amp)

Related Posts:

Example 6

A 10H.P (7.46kW) three phase squirrel cage induction motor of continuous rating using Star-Delta starting is connected through 400V supply by three single core PVC cables run in conduit from 250feet (76.2m) away from multi-way distribution fuse board. Its full load current is 19A. Average summer temperature in Electrical installation wiring is 35°C (95°F). Calculate the size of the cable for the motor?

Solution:

Now select the size of cable for full load motor current of 19A (from Table 4) which is 7/0.36” (23 Amperes) *(Remember that this is a 3-phase system i.e. 3-core cable) and the voltage drop is 5.3V for 100 Feet. It means we can use 7/0.036 cable according Table (4).

Now check the selected (7/0.036) cable with temperature factor in table (3), so the temperature factor is 0.97 (in table 3) at 35°C (95°F) and current carrying capacity of (7/0.036”) is 23 Amperes, therefore, current carrying capacity of this cable at 40°C (104°F) would be:

Current rating for 40°C (104°F) = 23 0.97 = 22.31 Amp.

Since the calculated value (22.31 Amp) at 35°C (95°F) is less than that of current carrying capacity of (7/0.036) cable which is 23A, therefore this size of cable (7/0.036) is also suitable with respect to temperature.

Load factor = 19/23 = 0.826

Now find the voltage drop for 100 feet for this (7/0.036) cable from table (4) which is 5.3V, But in our case, the length of cable is 250 feet. Therefore, the voltage drop for 250 feet cable would be;

Actual Voltage drop for 250feet = (5.3 250/100) 0.826 = 10.94V

And maximum Allowable voltage drop = (2.5/100) 400V= 10V

Here the actual Voltage drop (10.94V) is greater than that of maximum allowable voltage drop of 10V. Therefore, this is a not a suitable size of cable for the given load. So we will select the next size of selected cable (7/0.036) which is 7/0.044 and find the voltage drop again. According to Table (4) the current rating of 7/0.044 is 28 Amperes and the volt drop in per 100 feet is 4.1V (see Table 4). Therefore, the actual voltage drop for 250 feet cable would be;

Actual Voltage drop for 250 feet =

= Volt drop per 100 feet length of cable load factor

= (4.1/100) 250 0.826 = 8.46V

And Maximum Allowable voltage drop = (2.5/100) 400V= 10V

The actual voltage drop is less than that of maximum allowable voltage drop. So this is the most appropriate and suitable cable size for electrical wiring installation in a given situation.

Tables & Charts for Proper Cable & Wire Sizes – IEC

Below are the important tables which you should follow for determining the proper size of cable for Electrical Wiring Installation.

Click image to enlarge
Table-1-current-rating-of-Copper-cables-at-86F-or-30C

Click image to enlarge

Table-Chart-current-rating-of-flexible-cords-Copper-cables-at-86F-30CClick image to enlarge

How to Find The Suitable Size of Cable & Wire for Electrical Wiring Installation (Solved Examples in British and SI System)

Click image to enlarge

How to Find The Suitable Size of Cable & Wire |Solved Examples steb by step Click image to enlarge

Table-Cable-Size-Current-Rating-with-voltage-drop-Metric-Decimal-SI-System

NEC Wire Size Table 310.15(B)(16) (formerly Table 310.16) & Chart

NEC (National Electrical Code) Table 310.15(B)(16) (formerly Table 310.16) – 310.60 – ARTICLE 310 – Conductors for General Wiring & Allowable Ampacities of Conductors & Wire Sizes based on AWG (American Wire Gauge).

310.60               ARTICLE 310 — CONDUCTORS FOR GENERAL WIRING
Table 310.15(B)(16) (formerly Table 310.16) Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts, 60°C Through 90°C (140°F Through 194°F), Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)*
Size AWG or kcmil Temperature Rating of Conductor [See Table 310.104(A).] Size AWG or kcmil
60°C (140°F) 75°C (167°F) 90°C (194°F) 60°C (140°F) 75°C (167°F) 90°C (194°F)
Types TW, UF Types RHW, THHW, THW, THWN, XHHW, USE, ZW Types TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW,

THW-2, THWN-2, USE-2, XHH, XHHW,

XHHW-2, ZW-2

Types TW, UF Types RHW, THHW, THW, THWN, XHHW, USE Types TBS, SA, SIS, THHN, THHW,

THW-2, THWN-2, RHH, RHW-2, USE-2, XHH, XHHW, XHHW-2, ZW-2

COPPER ALUMINUM OR COPPER-CLAD ALUMINUM
18** 14
16** 18
14** 15 20 25
12** 20 25 30 15 20 25 12**
10** 30 35 40 25 30 35 10**
8 40 50 55 35 40 45 8
6 55 65 75 40 50 55 6
4 70 85 95 55 65 75 4
3 85 100 115 65 75 85 3
2 95 115 130 75 90 100 2
1 110 130 145 85 100 115 1
1/0 125 150 170 100 120 135 1/0
2/0 145 175 195 115 135 150 2/0
3/0 165 200 225 130 155 175 3/0
4/0 195 230 260 150 180 205 4/0
250 215 255 290 170 205 230 250
300 240 285 320 195 230 260 300
350 260 310 350 210 250 280 350
400 280 335 380 225 270 305 400
500 320 380 430 260 310 350 500
600 350 420 475 285 340 385 600
700 385 460 520 315 375 425 700
750 400 475 535 320 385 435 750
800 410 490 555 330 395 445 800
900 435 520 585 355 425 480 900
1000 455 545 615 375 445 500 1000
1250 495 590 665 405 485 545 1250
1500 525 625 705 435 520 585 1500
1750 545 650 735 455 545 615 1750
2000 555 665 750 470 560 630 2000
  •    *Refer to 310.15(B)(2) for the ampacity correction factors where the ambient temperature is other than 30°C (86°F). Refer to 310.15(B)(3)(a) for more than three current-carrying conductors.
  •    **Refer to 240.4(D) for conductor overcurrent protection limitations.

Here is the NEC table as a chart (image format to downloads as a reference)

Click image or open in a new tab to enlarge

NEC Table 310.15(B)(16) (formerly Table 310.16) - 310.60 - ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING & Allowable Ampacities of Conductors & Wire Sizes
NEC Table 310.15(B)(16) (formerly Table 310.16)
Wire Gauge Size & Wire Ampacity Table
AWG Wire Size Chart

Below is the general table based on NEC – 2020 with wire applications, rated ampacity and AWG wire size for given and specific uses.

Wire Applications Rated Ampacity Wire Gauge – AWG
Low-voltage lighting circuits 10 amps #18
Light duty Extension cords 13 amps #16
General lighting circuits, lamps and fixtures 15 amps #14
Kitchen, bathroom, and outdoor outlets and receptacles 20 amps #12
Electric water heaters, Electric ranges, stove, ovens, cooktops, dryers, air conditioners, 30 amps #10
Heavy duty Cooktops and ranges, EV Charging 40-50 amps #6
Commercial Electric furnaces, large electric heaters 60 amps #4

Related Posts:

Exit mobile version