HV And MV Switch Disconnectors And Isolators in Power System

HV/MV Switch Disconnectors And Isolators in Substation & Overhead Lines

Introduction HV/MV Switch Disconnectors And Isolators

High Voltage (HV) and Medium Voltage (MV)[1] installations require equipments to switching and/or isolating circuits or parts of circuits.

For that purpose switch-disconnectors and isolators are used. These equipments must comply with the following IEC[2] Standards:

Related Post: Difference between Circuit Breaker and Isolator / Disconnector

HV And MV Switch Disconnectors And Isolators in Power System

Switch Disconnectors

Switching operations can be performed through switch-disconnectors, equipments that are able to be operated on-load and can withstand and extinguish electric arc that is produced when the rated current of the installation is interrupted.

Switch-disconnectors are nowadays used only in MV installations, most commonly in MV switchgears and in MV overhead lines (see Figure 1) and they have usually an arcing chamber (air or SF6 insulated) to extinguish the arc, but they also perform that extinction in the air (Air Break SwitchABS).

Disconnecting-switch in overhead line

Figure 1 – Disconnecting-switch in overhead line

Characteristics of Switch Disconnectors

Main characteristics of switch-disconnectors are:

Switch-disconnectors may be mechanical (lever or crank) or motor operated (local or remote) and provided with earthing switches, mechanically interlocked, and release coils; some utilities used them associated with fuses for the protection of MV/LV[3] distribution power transformers (usually with rated power up to 630 kVA), as represented in Figure 2.Switch-disconnector associated with fuses

Figure 2 – Switch-disconnector associated with fuses

In these situations fuses must be equipped with acting strikers to mechanically open the switch-disconnector, to avoid the functioning of installation with only two phases; the switch-disconnector must have a tripping coil to allow the transformer protections to actuate.

Isolators

Isolators, also known as disconnectors, are used in HV and MV installations to isolate a circuit or parts of a circuit and to ensure, for safety reasons, to the operators and maintenance teams a visible interruption of the circuit.

Similar to MV switch-disconnectors, MV isolators are installed in MV switchgears and in MV overhead lines. HV isolators are generally installed outdoors, in AIS substations (Air Insulated Substation), seated in metallic structures, or indoors, in GIS substations (Gas Insulated Substation).

Isolators are not able to be withstand and to extinguish electric arc and they can only be operated off-load. If an isolator is operated on load an arc blast and an explosion can occur and provoke damages to persons and equipments.

Characteristics of Isolators

Main characteristics of isolators are:

Isolators may be mechanical or motor operated (local or remote) and may provided with earthing contacts, mechanically interlocked with main contacts. Usually earthing contacts are only mechanical operated. HV isolators may be single pole or three poles operated.

Motor is controlled by one closing coil and one opening coil, electrically interlocked. Limit switches are used to stop the motor when the isolator reaches its final positionopen or closed.

Local mechanical operation of isolators is usually an appellate maneuver, using a crank, which must suppress electrical control.

Mechanical and/or electrical interlocking must be provided to avoid on-load operations.

Symbols of Isolator and Disconnector

Types of HV Isolators

HV isolators are basically of three types:

Centre horizontal rotating isolatorFigure 3 – Centre horizontal rotating isolator

Double vertical rotating isolatorFigure 4 – Double vertical rotating isolator

Pantograph isolatorFigure 5 – Pantograph isolator

Pantograph isolators allow the connection of conductors at different levels and have the possibility to be decoupled for testing when the busbar is in operation.

Earthing isolatorFigure 6 – Earthing isolator

Earthing isolators are mostly used for busbar grounding.

During isolators testing is a good practice to place main contacts in a position between “opened” and “closed”, to avoid mechanical damages in the equipment if the connections of the motor are swapped over.

[1] Being Un the rated voltage of the network: HVUn ≥ 60 kV; MV1 kV < Un ≤ 49.5 kV.

[2] IEC: International Electrotechnical Comission.

[3]LV: Low Voltage. Un ≤ 1 kV.

About the Author: Manuel Bolotinha

About the Author: Manuel Bolotinha

-Licentiate Degree in Electrical Engineering – Energy and Power Systems (1974 – Instituto Superior Técnico/University of Lisbon)
– Master Degree in Electrical and Computers Engineering (2017 – Faculdade de Ciências e Tecnologia/Nova University of Lisbon)
– Senior Consultant in Substations and Power Systems; Professional Instructor

You may also read:

Exit mobile version